Norden's Ultra power series 160-200 kVA UPS is an online double conversion UPS that has three-phase in both input and output and a unity output power factor. This features a maximum parallel expanded operation of up to 6 units and has an inverter efficiency upto 96% makes it suitable for data center applications.
Norden's Ultra power series 160-200 kVA UPS is an online double conversion UPS that has three-phase in both input and
output and a unity output power factor. This features a maximum parallel expanded operation of up to 6 units and has
an inverter efficiency upto 96% makes it suitable for data center applications.
| Model | CN933160U / CN933160U-5L | CN933180U / CN933180U-5L | CN933200U / CN933200U-5L | |
Capacity | kVA | 160 | 180 | 200 |
Watts | 160K | 180K | 200K | |
Input | Normal Voltage | 380/400/415Vac (3Ph+N+PE) | ||
| Operating voltage range | 138~305Vac for 40% Load; 305~485Vac for Full Load | |||
| Harmonic distortion(THDi) | <3%(100% linear load) | |||
| Operating frequency range | 40~70Hz | |||
| Power factor | ≥0.99 | |||
| Bypass voltage range | 220Vac Max.Voltage:+25% (optional +10%,+15%,+20%) 230Vac Max.Voltage:+20%(optional +10%,+15%) 240Vac Max.Voltage:+15%(optional +10%) Min.Voltage:-45%(optional -15%,-20%,-30%)
| |||
| Bypass Frequency range | Frequency synchronize tracing range:±10% | |||
| Generator input | Support | |||
Output | Rated voltage | 380/400/415Vac (3Ph+N+PE) | ||
| Power factor | 0.9 | |||
| Voltage regulation | ±1% | |||
| Frequency Line mode | ±1%/±2%/±4%/±5%/±10% of the rated frequency (Optional) | |||
| Frequency Bat. mode | 50/60(±0.2%)Hz | |||
| Crest factor | 3:1 | |||
| Harmonic distortion (THDv) | ≤2% with linear load, ≤4% with non-linear load | |||
| Efficiency | 95.5% | |||
| Output Waveform | Pure Sine Wave | |||
Battery | Rated voltage | ±180/±192/±204/±216/±228/±240/±252/±264/±276/±288/±300Vdc(30/32/34/36/38/40/42/44/46/48/50pcs) | ||
| Charging current (Charging current can be set according to the battery capacity installed) | 60A | 80A | ||
System Features | Transfer time | Mains to battery:0ms; Inverter to bypass:0ms
| ||
| Overload Line mode | ≤110%: Overload 60min, ≤150%: Overload 1min, >150% 1.2s turn to bypass mode immediately | |||
| Overload Bypass mode | 30°C: 135% Overload long term; 40°C: 125% Overload long term >1000%, 100ms
| |||
| Backfeed Protection | Support | |||
| Alarm | Overload, utility abnormal, UPS fault, battery low, etc | |||
| Protection | Short circuit, overload, over-temperature, battery low, fan fault alarm | |||
| Remote LCD | Support | |||
| Communication | USB, RS232, RS485, Parallel port,dry contact, Intelligent slot, LBS, SNMP card (optional), Relay card (optional)
| |||
Environment | Operating temperature | 0~40°C | ||
| Storage temperature | -25~55°C | |||
| Humidity range | 0~95% (Non-condensing) | |||
| Altitude | <1500m | |||
| Noise level | <63dB | 64 | <66db | |
Physical | Dimension WxDxH(mm) | 442x850x1200 | ||
| Net Weight (kg) | 200 | 220 | 280 | |
Standards | Safety | CE; IEC/EN62040-1,IEC/EN62477-1
| ||
| EMC | IEC/EN 62040-2 (IEC 61000-2-2, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8,
IEC61000-4-11) | |||
| Part Number | Description | ||
| CN933160U | 160kVA Double Conversion Transformer-less 3/3 UPS (External Battery)
| ||
| CN933160U-5L | 160kVA Double Conversion Tower Type 3/3 UPS with 7inch LCD display (External Battery) | ||
| CN933180U
| 180kVA Double Conversion Transformer-less 3/3 UPS (External Battery) | ||
| CN933180U-5L | 180kVA Double Conversion Tower Type 3/3 UPS with 7inch LCD display (External Battery) | ||
| CN933200U | 200kVA Double Conversion Transformer-less 3/3 UPS (External Battery)
| ||
| CN933200U-5L | 200kVA Double Conversion Tower Type 3/3 UPS with 7inch LCD display (External Battery) | ||
| Part Number | Description | ||
| CNS01 | SNMP Card | ||