CATEGORY 6A F/UTP 4-PAIR PLENUM CABLE, CMP

Norden Category 6A F/UTP plenum(CMP) cables exceed Category 6A/Class E specification. It is tested to 500 MHz frequency range and designed to support 10 Gigabyte applications to full 100 m.Extremely high pair-balance providing excellent EMC (Electro Magnetic compatibility), minimizing radiation, maximizing noise immunity and providing high alien cross talk performance to F/UTP cabling systems. F/UTP (Twisted Pair - overall Foil shield) cabling systems are installed for improved Alien Cross talk performance.

Norden Category 6A F/UTP plenum(CMP) cables exceed Category 6A/Class E specification. It is tested to 500 MHz frequency range and designed to support 10 Gigabyte applications to full 100 m.Extremely high pair-balance providing excellent EMC (Electro Magnetic compatibility), minimizing radiation, maximizing noise immunity and providing high alien cross talk performance to F/UTP cabling systems. F/UTP (Twisted Pair - overall Foil shield) cabling systems are installed for improved Alien Cross talk performance.



MATERIAL CONSTRUCTION & DESIGN

Conductor Material

Solid Bare Copper

Conductor Size

23 AWG

Conductor Construction

Solid

Insulation Material

FEP

Nom. Thickness

0.25±0.05mm

Insulation Diameter

1.10±0.05mm

Conductor Unit Identification

Solid/Stripe

Colour Code

Per TIA/EIA 568-B

Tape

PET

Drain Wire

 24AWG Solid Tin Copper

Screening Material

 Aluminium/Polyester Foil

Screening Design

100% Coverage with 25% Overlapping

Total Number of Wires

8

Separator

FEP CROSSWEB

Rip Cord

Yes

Outer Jacket

Plenum PVC

Outer Jacket Thickness & Ex. Diameter

0.5mm, 7.4±0.30mm

Outer Jacket Colour

As Per Requirement

Marking

Per Requirement


ELECTRICAL & MECHANICAL CHARACTERISTICS

Frequency Range

1 - 500 MHz

Impedance

100±150

Coupling Attenuation

≥ 55 dB

Max. DC Resistance

9.380/100m

Max. Resistance Unbalance

≤5%

Capacitance

<5.6nF/100m

Capacitance Unbalance

1600pF/km

Propagation Delay Skew

45ns/100m

Velocity of propagation

≥67%

Dielectric Strength

DC-1KV/1 Min

Dielectric Strength to Shield

DC-1KV/1 Min

Voltage Rating

300V

Max. Tensile Strength 

Short Term: 110N

Min. Bend Radius

8*OD

Operating Temperature Range

-20°C to +75°C


TRANSMISSION PERFORMANCE

*Supplied cables meet Cat. 6a min. transmission requirements as per IEC 61156-5 Ed. 2

Cat 6a Cable Performance Table
Freq.
MHz
Attenuation
dB/100m @ 20°C
NEXT
dB
PS NEXT
dB
RL
dB
ACR-F
dB
PS ACR-F
dB
12.174.372.320.067.864.8
43.865.363.323.055.852.8
105.360.858.825.049.746.7
165.959.357.325.047.844.8
207.557.855.825.045.840.7
259.453.351.324.339.836.8
31.2510.552.950.923.638.035.0
62.515.047.445.421.531.928.9
10019.144.342.320.127.824.8
20027.639.837.818.021.818.8
25031.138.336.317.319.816.8
30034.337.135.116.818.315.3
40040.135.333.315.915.812.8
50045.333.831.815.213.810.8
*Supplied cables meet Cat. 6a min. transmission requirements as per IEC 61156-5 Ed. 2
Part NumberDescriptionStandard Length
114-18001204XCategory 6A F/UTP 4-Pair Plenum Cable, CMP305 m

X: BK(Black), BL(Blue), GN(Green), GY(Gray), RD(Red), WH(White), YL(Yellow)