The shielded power limited fire protective fire alarm signal cable from Norden is suitable to use for installation in signalling & fire alarm systems. This cable is constructed with Polypropylene ( PP ) Insulation, 120 % Al-Polyester Foil Shield with FR-PVC ( FPLR ) protective outer jacket.
The shielded power limited fire protective fire alarm signal cable from Norden is suitable to use for installation in signalling & fire alarm systems. This cable is constructed with Polypropylene ( PP ) Insulation, 120 % Al-Polyester Foil Shield with FR-PVC ( FPLR ) protective outer jacket.


| Characteristics | Value | ||
| No. of Conductor | 2 | ||
| Conductor Size | 1.29 ± 0.005 mm , 16AWG | ||
| Insulation Diameter | 2.1 ± 0.05 mm | ||
| Drain Wire Size | 7 x 0.25 mm | ||
| Jacket Thickness | 0.8 mm | ||
| Jacket Diameter | 6.0 ± 0.3 mm | ||
| Max. Recommended Pulling Tension | 27 KG | ||
| Min. Bending Radius | 10 x OD | ||
| Operating Temperature | -20°C to +70°C | ||
| Characteristics | Value | Unit |
| Nom. Conductor DCR | 13.7 | Ω/KM |
| Dielectric Strength between Pairs | 2.5 | KV |
| Max. Operating Voltage | 300 | V |
| Sparker Test | 3000 | VAC |
| Characteristics | Value | ||
| Test Material | FRPVC | ||
| Before Tensile Strength (Mpa) | 10.3 | ||
| Aging Elongation (%) | 100 % | ||
| After Tensile Strength (Mpa) | 6.7 | ||
| Aging Elongation (% of unaged) | 65 | ||
| Cold Bend (-20°C x 4 hrs) | No Crack | ||
| Standard & Environmental | UL 1424 | ||
| Part Number | Description |
| 75-4202165 | 2 Core 16AWG Shielded Fire Alarm Cable PP Insulation FRPVC Jacket |