2 Core 1.2 mm² Shielded Multi Conductor Cable FRPVC

Norden Shielded Multi Conductor Cable is engineered for reliable signal transmission in critical control, instrumentation, and low-voltage power applications. Designed with dual layers of mica tape for flame protection, the cable features XLPE (cross-linked polyethylene) insulation for excellent thermal and electrical performance. A 100% coverage aluminium-mylar (Al-Mylar) tape shield ensures superior protection against EMI/RFI interference. The cable is finished with a robust, flame-retardant FRPVC outer jacket, making it suitable for applications where enhanced safety are essential.

Norden Shielded Multi Conductor Cable is engineered for reliable signal transmission in critical control, instrumentation, and low-voltage power applications. Designed with dual layers of mica tape for flame protection, the cable features XLPE (cross-linked polyethylene) insulation for excellent thermal and electrical performance. A 100% coverage aluminium-mylar (Al-Mylar) tape shield ensures superior protection against EMI/RFI interference. The cable is finished with a robust, flame-retardant FRPVC outer jacket, making it suitable for applications where enhanced safety are essential. 

CABLE CONSTRUCTION


PHYSICAL CHARACTERISTICS

CharacteristicValue

No. of Conductor

2

Conductor Size

1.2 mm² ( 60/0.16 )

Insulation 1 Thickness
0.15 mm 
Insulation 2 Thickness 0.8 mm
Insulation Diameter 3.65 mm 
Drain Wire Size7/0.20

Jacket Thickness

0.8 mm

Jacket Diameter
8.8 mm

Max. Recommended Pulling Tension

300N

Bending Radius

89 mm

Operating Temperature 
0˚C to +60˚C
 


ELECTRICAL CHARACTERISTICS

CharacteristicUnitValue
Nom. Capacitance Cond. to Cond
pF/m
90
Nom. Capacitance Cond. to Cond. & ShieldpF/m210
DCR Conductor
Ω/km
≤15
DCR Shield Ω/Km≤82
Dielectric Strength MV/min≥30 
Max. Recommended Current A15
Max. Operating VoltageV300/500 

MECHANICAL CHARACTERISTICS

CharacteristicValue

Test Material

FRPVC

Before Tensile Strength (Mpa)

≥ 13.8

Aging Elongation (%)

≥ 100

After Tensile Strength

≥ 70%

Aging Elongation (%)

≥ 45

Cold Bend (-20±°C x 4 hrs)

No Crack

INSULATION COLOR CODE

Individual CoreColour

Core 1

Black

Core 2
White

Part NumberDescriptionNet Weight (Kg/Km)
71-M202125 
2 Core 1.2 mm² Shielded Multi Conductor Cable FRPVC
80