10-40KVA Online Tower UPS With Internal Batteries

The online UPS ensures seamless, high-efficiency power backup by stabilizing the power supply and instantly switching to battery during outages. Supporting both single-phase and three-phase input/output congurations, it provides a reliable and energy-efficient solution for commercial buildings, data centers, and industrial environments requiring uninterrupted and consistent power.

The online UPS ensures seamless, high-efficiency power backup by stabilizing the power supply and instantly switching to battery during outages. Supporting both single-phase and three-phase input/output congurations, it provides a reliable and energy-efficient solution for commercial buildings, data centers, and industrial environments requiring uninterrupted and consistent power.

UPS Specification Table
MODEL NPS-AC10T33I NPS-AC15T33I NPS-AC20T33I NPS-AC30T33I NPS-AC40T33I
Rated Power 10kVA 15kVA 20kVA 30kVA 40kVA
Input Normal Voltage 380/400/415VAC(L-L) 220/230/240VAC(L-N)
Voltage Range 304-478VAC(L-L) full load 304-228VAC(L-L) power derate from 100% to 50%
Frequency 50/60Hz (40-70Hz)
Power Factor >0.99
Current Distortion THDi<2% (100% Linear load) THDi<3% (100% Linear load)
Output Output Voltage 380/400/415VAC(L-L) 220/230/240VAC(L-N)
Power Factor 1
Voltage Regulation ±1.0%
Frequency Accuracy 0.1%
Current Crest Ratio 3:1
Harmonic Distortion <1% linear load, <5% non-linear load according to IEC 62040-3
Phase Accuracy 120°±0.5°
Waveform Sine wave
Output Socket Type No sockets, output terminal
Overload Normal Mode 110%,1 hour; 125%,10 mins; 150%,1 min; >150%,200ms
Bypass Mode 110%,1 hour; 125%,10 mins; 150%,1 min; >150%,200ms
Battery Model 12VDC/9Ah
Quantity 40 PCS 80 PCS
Charging Capacity 8.6%*Pout 5.7%*Pout 20%*Pout
Charging Accuracy ±1%
Bypass Rate Voltage 380/400/415VAC(L-L) 220/230/240VAC(L-N)
Frequency Range 50/60Hz Settable ±1Hz ±3Hz ±5Hz
Voltage Range Range -40% ~ +25%, Settable, default -20% +15%
Management Display LED + 7 inch touch LCD
Communication Interface USB, RS232, RS485, Dry contact, Air filter, Cold start, Internet port USB, RS232, RS485, Dry contact, Cold start
Optional Features SNMP card, Relay contact card, Parallel kit SNMP card, Relay contact card, Parallel kit, Air filter
Alarm Two short, One long General alarm (for example: main input abnormal)
Continuous Alarm Serious faults (for example: fuse or hardware fault)
Indicators Green System is working normally
RedSystem fails or fault
YellowSystem warns (utility fails, over load, etc)
Environment Humidity 0-95% (Non-condensing )
Noise level 67~72dB at full load
IP rating IP20
Operating Temperature0-40°C
Storage Temperature-25 ~70 °C
Altitude≤3000m above sea level, derate power by 2% per 100m between 3000m and 4000m
Physical
Dimension WxDxH (mm) 250*694*724 400*770*854 350*823*1200
Weight (kg)140250262
Standard Safety IEC62040-1, IEC60950-1
EMC IEC62040-2 IEC61000-4-2(ESD) IEC61000-4-3(RS) IEC61000-4-4 (EFT) IEC61000-4-5 (Surge)
Part NumberDescription
NPS-AC10T33I
10kVA Online Tower 3/3,3/1 UPS, 7inch screen with SNMP function, 40x battery space (Without Battery)
NPS-AC15T33I15kVA Online Tower 3/3,3/1 UPS, 7inch screen with SNMP function, 40x battery space (Without Battery)
NPS-AC20T33I20kVA Online Tower 3/3,3/1 UPS, 7inch screen with SNMP function, 40x battery space (Without Battery)
NPS-AC30T33I30kVA Online Tower 3/3,3/1 UPS, 7inch screen with SNMP function, 80x battery space (Without Battery)
NPS-AC40T33I40kVA Online Tower 3/3,3/1 UPS, 7inch screen with SNMP function, 80x battery space (Without Battery)