Norden Armoured Fire Resistant Speaker Cable is designed for reliable voice and audio transmission in fire alarm, public address, and voice evacuation systems during fire conditions. It uses stranded bare copper conductors with mica tape and PE insulation to maintain circuit integrity under fire. The cable is protected by galvanized steel wire armour and a PVC inner sheath, providing strong mechanical and rodent protection. The FR-LSZH outer jacket provides enhanced safety.

Norden Armoured Fire Resistant Speaker Cable is designed for reliable voice and audio transmission in fire alarm, public address, and voice evacuation systems during fire conditions. It uses stranded bare copper conductors with mica tape and PE insulation to maintain circuit integrity under fire. The cable is protected by galvanized steel wire armour and a PVC inner sheath, providing strong mechanical and rodent protection. The FR-LSZH outer jacket provides enhanced safety. 

CABLE CONSTRUCTION


STANDARD COMPLIANCE

IEC60331

PHYSICAL CHARACTERISTICS

CharacteristicValue
No. of Conductor
2
Conductor Size 1.5mm², 30x0.25mm 
PE Insulation Thickness 0.70mm
Insulation Diameter4.2±0.5 mm
Bedding Dia 10.3mm
Steel Wire Size 0.9mm
 Outer Jacket Thickness1.4mm
Outer Jacket Dia 14.9mm
 


ELECTRICAL CHARACTERISTICS

CharacteristicValue
Max DC Resistance
≤12.5 ohms/KM
Min. Insulation resistance5000 M.ohms X Km
Operating Voltage 600/1000V
Testing Voltage 3500V
Operating Temp-20°C to +75°C
Min. Bending radius20xOD

MECHANICAL CHARACTERISTICS

Characteristics
Value
Test Material
FR-LSZH
Before Tensile Strength (Mpa)
≥9.8
Aging Elongation (%)
≥125
Aged Tensile Strength [Mpa)
≥8.0
Aging Elongation (%) 
≥100%
Part NumberDescription
NC28-326310215SX
2 Core 1.5 Sq.mm Galvanized Steel Wire Armoured Fire Resistant Speaker Cable Inner PVC / Outer FR-LSZH