LOOP EXTENSION MODULE NFA-T01LM

The NFA-T01LM loop extension module operates on a DC24V power supply and utilizes an internal electrical isolation circuit to achieve real-time isolation and transmission of input and output bus signals, delivering a standard bus waveform. This module enhances the bus’s resistance to interference and helps extend the communication range. It is particularly effective in environments where external interference occurs or where longer communication distances are required. Compliant with EN 54 Part 18 (European Standard), the unit features a discreet design suitable for modern buildings. Its plug-in assembly allows easy installation and maintenance.

The NFA-T01LM loop extension module operates on a DC24V power supply and utilizes an internal electrical isolation circuit to achieve real-time isolation and transmission of input and output bus signals, delivering a standard bus waveform. This module enhances the bus’s resistance to interference and helps extend the communication range. It is particularly effective in environments where external interference occurs or where longer communication distances are required. Compliant with EN 54 Part 18 (European Standard), the unit features a discreet design suitable for modern buildings. Its plug-in assembly allows easy installation and maintenance.

FEATURES & BENEFITS

  • EN54-18 Compliance
  • Built-in MCU processor
  • Input bus, the output bus signal between the electrical isolation, electromagnetic interference has a good inhibitory capacity, stable and reliable work Input Fire or Supervisory signal configuration
  • LED status indicator
  • To correct the bus signal, the output standard bus waveform
  • Fast intelligent bus output short circuit judge function, bus output short circuit protection function; after the bus is normal, it can recover the bus output in time
  • Aesthetically pleasing design

  • TECHNICAL INFORMATION

    Characteristic

    Value

     Compliance EN 54-18
     Input Voltage

    Loop Power: 24VDC [16V to 28V]

    External PSU: 20 to 28VDC

    Current Consumption

    Loop: ≤5mA

    External PSU: ≤500mA

    Bus Input Range ≤1000m
    Bus Output Range≤1000m
     Most Cascade3
     Protocol / Addressing  Norden, Value range from 1 to 254
    Indicator StatusNormal: Single blink / Fault: Steady-on
     Material / Colour Metal / Gray
    Dimension / LWH   155.0mm×97.0mm×40.0mm
     Operating Temperature  -10°C to +55°C
     Humidity 0 to 95% Relative Humidity, Non condensing

    ORDERING INFORMATION

    Part Number

    Description

    NFA-T01LMLOOP EXTENSION MODULE