2 Core 16 AWG Unshielded Multi Conductor PP Insulation Cable

Norden Unshielded Multi Conductor Cable is suitable to use within Commercial Audio Systems, Control and Instrumentation purpose. The cable is constructed with PP insulation, Nylon Rip Cord and PVC/LSZH Outer Jacket.

Norden Unshielded Multi Conductor Cable is suitable to use within Commercial Audio Systems, Control and Instrumentation purpose. The cable is constructed with PP insulation, Nylon Rip Cord and PVC/LSZH Outer Jacket.

CABLE CONSTRUCTION


PHYSICAL CHARACTERISTICS

CharacteristicValue

No. of Conductor

2

Conductor Size

16 AWG, 19x0.29mm

Insulation Thickness 0.3mm
Insulation Diameter 2.05±0.05mm
Jacket Thickness0.5mm
Jacket Diameter 5.0±0.3mm
Max. Recommended Pulling Tension200 N
 Min. Bending Radius 10OD
Operating Temperature-20°C to +70°C

 

ELECTRICAL CHARACTERISTICS

CharacteristicUnitValue

Nom. Conductor DCR

Ω/km

14.4

Nom. Capacitance Conductor to Conductor

pF/m

50±15

Max. Recommended Current @ 25°C

Amps

6.25

Max. Operating VoltageV 300

MECHANICAL CHARACTERISTICS

CharacteristeicsValue
Test Material PVC/LSZH
Before Tensile Strength (Mpa)16
 Aging Elongation (%)300%
 After Tensile Strength (Mpa) ≥4.5
Aging Elongation (%)≥75%
Cold BendNo Crack


INSULATION COLOUR CODE

Individual CoreColour

Core 1

Black

Core 2

White

Part NumberDescription Net Weight (Kg/Km)
71-4102161 2 Core 16 AWG Unshielded Multi Conductor PP Insulation Cable, PVC41
 71-41021622 Core 16 AWG Unshielded Multi Conductor PP Insulation Cable, LSZH41