SILICONE INSULATED UNSHIELDED FIRE-RESISTANT CABLE

NORDEN silicone + mica tape-insulated fire-resistant cables are manufactured to meet the specific requirements of fire-resistant cable standards. These cables ensure reliable circuit integrity, keeping emergency evacuation systems operational even while the cable is burning.

NORDEN silicone + mica tape-insulated fire-resistant cables are manufactured to meet the specific requirements of fire-resistant cable standards. These cables ensure reliable circuit integrity, keeping emergency evacuation systems operational even while the cable is burning.

CABLE CONSTRUCTION



ParametersStandads
 Flame Tests IEC /EN 60332-1
Insulation Integrity IEC 60331-21, BS 6387 Category C-3 Hours Fire Test 950°C)


ELECTRICAL & MECHANICAL CHARACTERISTICS

ParametersValue
 2 Cross Section (mm²)1.5mm² 2.5 mm²  
Conductor (Cu)2x27/0.252x50/0.24
Conductor Resistance (max. Ω /km)13.537.93
Insulation Thickness (mm)0.450.42 
Insulation Outer Dia (mm)2.402.80 
Minimum Insulation Resistance @ 0°C200 MΩ x Km
Operating Voltage300/500V
Breakdown Test Voltage2000V
Temperature Range-40 to 90°C


PHYSICAL INFORMATION

Nom. Cond. Cross-Sect. (mm] Conductor Size (no./mm) Outer Sheath Thickness (mm)Outer Cable Diameter (mm)
1 Pair x 1.5mm²27/0.250.856.8
1 Pair x 2.5mm²50/0.240.907.8
Part NumberDescription
8N-01250121 Pair 2.5mm² Silicone Insulated Unshielded Fire Resistant Cable
8N-01150121 Pair 1.5mm² Silicone Insulated Unshielded Fire Resistant Cable