6~10kVA Online Tower Split Phase UPS

The Maxion Series Split-Phase Online Tower UPS delivers high-efficiency, continuous power protection for critical loads requiring split-phase output. It provides exible runtime scalability to meet a wide range of application needs. Engineered for maximum reliability, the system features true online double-conversion technology, wide input voltage tolerance, and a unity output power factor. With stable split-phase output and zero transfer time, it ensures uninterrupted operation, safeguarding sensitive and mission-critical equipment from power disturbances.

The Maxion Series Split-Phase Online Tower UPS delivers high-efficiency, continuous power protection for critical loads requiring split-phase output. It provides exible runtime scalability to meet a wide range of application needs. Engineered for maximum reliability, the system features true online double-conversion technology, wide input voltage tolerance, and a unity output power factor. With stable split-phase output and zero transfer time, it ensures uninterrupted operation, safeguarding sensitive and mission-critical equipment from power disturbances. 

SPECIFICATIONS

MODELNPS-AC06SPT264ENPS-AC10SPT264E
CapacitykVA6kVA10kVA
Watts6000W10000W
PhaseSingle phase with ground
InputNormal Voltage220VAC/230VAC/240VAC
Voltage range110~300VAC
Frequency range50/60Hz±5Hz
Power factor≥0.99
Cold startDefault frequency 60Hz
OutputOutput Voltage220/230/240V
Power Factor1
Voltage Regulation±1%
Frequency range (Batt.mode)50/60Hz
Current crest ratio3:1
Harmonic distortion≤2%, linear load
≤5%, non-linear load
WaveformSine wave
Output Socket Typestandard with terminal
EfficiencyNormal modeup to 92.5%

ECO modeup to 96.5%
BatteryQuantity16-20
Max charging12A
Rate voltage      Internal BatteryDefault 192VDC settable
                         External BatteryDepend on the capacity of external batteries 
OverloadNormal mode110%:10mins;130%:1min;150%:30 seconds (Transfer to bypass)
AlarmBattery modeBeeping every second
Battery lowBeeping every second
Display indicatorsLoad level, battery level, AC mode, Bypass mode and fault indicators
FaultContinuously beeping
ManagementDisplayLED+LCD
Communication interfaceRS232, EPO, RS485, Cold start
Optional featuresRelay contact card, SNMP card, USB, Parallel kit
EnvironmentHumidity0-95% non-condensing
IP ratingIP 20
Operating Temperature0-40℃,no derating
Storage Temperature0-70℃
Altitude Up to 1000m without derating 
PhysicalDimension WxDxH (mm)250*734*596
Weight (kg)85110
StandardsSafetyCE; IEC/EN62040-1,IEC/EN62477-1
EMCIEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8, IEC61000-4-11,IEC61000-2-2

EXTERNAL BATTERY PACK

MODELNPS-ACBP16192VDCNPS-ACBP20240VDC
BATTERY SYSTEM
Battery typeVRLA (Valve Regulated Lead Acid Battery - SMF)
Typical battery recharging time6~8 hours (to 90% of full capacity)
Typical battery life3~5 years, depend on discharging cycle and ambient temperature
System voltage192Vdc240Vdc
Battery quantity1620
Capacity12V/9Ah
PHYSICAL
Dimension W x D x H (mm)200 x 493 x 338
Net weight (kg)5060
ENVIRONMENT
Operating environment0°C~40°C
Relative humidity0~95% (Non condensing)
Part NumberDescription
NPS-AC06SPT264E
6kVA Online Tower Split Phase UPS, 192-264VDC (External Battery)
NPS-AC06SPT192I6kVA Online Tower Split Phase UPS, with battery, 7Ah/12v*16 (Internal Battery)
NPS-AC10SPT264E10kVA Online Tower Split Phase UPS, 192-264VDC (External Battery)
NPS-AC10SPT192I10kVA Online Tower Split Phase UPS, with battery, 9Ah/12v*16 (Internal Battery)
NPS-ACBPT16192VDC192VDC 16x9Ah Tower Type Battery Pack
NPS-ACBPT20240VDC240VDC 20x9Ah Tower Type Battery Pack

COMPATIBLE ACCESSORIES

Part NumberDescription
NPS-ACSN01
Smart SNMP Card
NPS-ACIOT01CIoT Card for Maxion Series UPS
NPS-ACP15MParallel kit for 1Ph, 5m