Norden Category 6A F/UTP plenum(CMP) cables exceed Category 6A/Class E specification. It is tested to 500 MHz frequency range and designed to support 10 Gigabyte applications to full 100 m.Extremely high pair-balance providing excellent EMC (Electro Magnetic compatibility), minimizing radiation, maximizing noise immunity and providing high alien cross talk performance to F/UTP cabling systems. F/UTP (Twisted Pair - overall Foil shield) cabling systems are installed for improved Alien Cross talk performance.
Norden Category 6A F/UTP plenum(CMP) cables exceed Category 6A/Class E specification. It is tested to 500 MHz frequency range and designed to support 10 Gigabyte applications to full 100 m.Extremely high pair-balance providing excellent EMC (Electro Magnetic compatibility), minimizing radiation, maximizing noise immunity and providing high alien cross talk performance to F/UTP cabling systems. F/UTP (Twisted Pair - overall Foil shield) cabling systems are installed for improved Alien Cross talk performance.

Conductor Material | Solid Bare Copper |
Conductor Size | 23 AWG |
Conductor Construction | Solid |
Insulation Material | FEP |
Nom. Thickness | 0.25±0.05mm |
Insulation Diameter | 1.10±0.05mm |
Conductor Unit Identification | Solid/Stripe |
Colour Code | Per TIA/EIA 568-B |
Tape | PET |
Drain Wire | 24AWG Solid Tin Copper |
Screening Material | Aluminium/Polyester Foil |
Screening Design | 100% Coverage with 25% Overlapping |
Total Number of Wires | 8 |
Separator | FEP CROSSWEB |
Rip Cord | Yes |
Outer Jacket | Plenum PVC |
Outer Jacket Thickness & Ex. Diameter | 0.5mm, 7.4±0.30mm |
Outer Jacket Colour | As Per Requirement |
Marking | Per Requirement |
Frequency Range | 1 - 500 MHz |
Impedance | 100±150 |
Coupling Attenuation | ≥ 55 dB |
Max. DC Resistance | 9.380/100m |
Max. Resistance Unbalance | ≤5% |
Capacitance | <5.6nF/100m |
Capacitance Unbalance | 1600pF/km |
Propagation Delay Skew | 45ns/100m |
Velocity of propagation | ≥67% |
Dielectric Strength | DC-1KV/1 Min |
Dielectric Strength to Shield | DC-1KV/1 Min |
Voltage Rating | 300V |
Max. Tensile Strength | Short Term: 110N |
Min. Bend Radius | 8*OD |
Operating Temperature Range | -20°C to +75°C |
*Supplied cables meet Cat. 6a min. transmission requirements as per IEC 61156-5 Ed. 2
| Freq. MHz |
Attenuation dB/100m @ 20°C |
NEXT dB |
PS NEXT dB |
RL dB |
ACR-F dB |
PS ACR-F dB |
|---|---|---|---|---|---|---|
| 1 | 2.1 | 74.3 | 72.3 | 20.0 | 67.8 | 64.8 |
| 4 | 3.8 | 65.3 | 63.3 | 23.0 | 55.8 | 52.8 |
| 10 | 5.3 | 60.8 | 58.8 | 25.0 | 49.7 | 46.7 |
| 16 | 5.9 | 59.3 | 57.3 | 25.0 | 47.8 | 44.8 |
| 20 | 7.5 | 57.8 | 55.8 | 25.0 | 45.8 | 40.7 |
| 25 | 9.4 | 53.3 | 51.3 | 24.3 | 39.8 | 36.8 |
| 31.25 | 10.5 | 52.9 | 50.9 | 23.6 | 38.0 | 35.0 |
| 62.5 | 15.0 | 47.4 | 45.4 | 21.5 | 31.9 | 28.9 |
| 100 | 19.1 | 44.3 | 42.3 | 20.1 | 27.8 | 24.8 |
| 200 | 27.6 | 39.8 | 37.8 | 18.0 | 21.8 | 18.8 |
| 250 | 31.1 | 38.3 | 36.3 | 17.3 | 19.8 | 16.8 |
| 300 | 34.3 | 37.1 | 35.1 | 16.8 | 18.3 | 15.3 |
| 400 | 40.1 | 35.3 | 33.3 | 15.9 | 15.8 | 12.8 |
| 500 | 45.3 | 33.8 | 31.8 | 15.2 | 13.8 | 10.8 |
| Part Number | Description | Standard Length |
| 114-18001204X | Category 6A F/UTP 4-Pair Plenum Cable, CMP | 305 m |
X: BK(Black), BL(Blue), GN(Green), GY(Gray), RD(Red), WH(White), YL(Yellow)